On the alarm summary page, all alarms were showing same date and time stamps as of the latest alarm has.

You can display the alarm summary state entries on summary page you need to set the following INI parameters in CItect.ini file
1. [Alarm]SumStateFix = 1
2. [Alarm]SavePeriod = 100