How to set the parameter 4W or 2W+ULP in Micrologic 6A of Masterpact ACB.

The HMI of Micrologic A doesn't manage 4W or 2W+ULP you need to connect the trip unit to RSU software and after that in configuration mode of RSU you will be able to choose 4W or 2W+ULP. 