To know how many times the circuit breaker on channel 2 of Acti9 Smartlink has tripped, which modbus register i need to read.

On 14254 modbus register address you can read how many times the circuit breaker on channel 2 of Acti9 Smartlink has tripped.
Refer attached Table of Modbus Register for Summary Description of Channels 1 to 11 of the Acti 9 Smartlink Device.