Technical FAQs

Ask a Question

Can i use 140NOE77100 or 140CRP31200 for synchronizing PLC time with NTP server.

140NOE77100 or 140CRP31200 modules can not sync PLC time with NTP server. You have to use 140 NOE77111 or 140NOC78*** modules for synchronization of PLC time with NTP server connected to some other module on the PLC rack.
Was this helpful?
What can we do to improve the information ?