How can I show hardware alarms in Power SCADA Expert.

To show the Hardware alarms in Power SCADA Expert you need to call the PageAlarm(255) or PageSummary(255) functions to display alarm or summary page during runtime, as the hardware alarms have the a default Alarm Category of 255. 