Is trip circuit supervision possible in masterpact NW breaker using DC Shunt coil.

The MX release has an electronic control circuit and  wiring is done at  MX input terminal you do not reach directly the coil itself, you connect to the MX electronic control circuit, and it is not a linear circuit. so trip circuit supervision is not possible in shunt coil in masterpact NW breaker.

 