What is the rated service breaking capacity Ics of C60 UL1077 range of MCB.
AS per IEC 60947, the Ics value of the circuit breaker is in terms of the % of ICU rating. The Ics value of the
C60UL 1077 offer is equal to 75% of Icu rating.
FA143551 |
30-Mar-2012
|
Standards
PDF
Email
Bookmark
Print
Answers which others found helpful
> Does Multi 9 C60 MCBs are in compliance to UL94 (body material).
> If the C60H circuit breaker is locked ON with the MGLA padlocking facility will it still trip under fault conditions.
> Can the Multi 9 range MCB be reverse fed.