FAQ Search

What are the Contact Resistance values for the LF range MV Circuit Breaker.

The contact resistance values for the LF range MV Circuit Breaker are tabulated below :

 
LF LF1 LF2 LF3

Fixed

Withdrawable

Fixed

Withdrawable

Fixed

Withdrawable

Contact Resistance

current supplied : I = 100 A

< 33 µΩ < 50 µΩ < 37 µΩ < 45 µΩ < 14 µΩ < 26 µΩ
FA22647  |  12-Jul-2012
  • Please rate the content of this information
    Unhelpful 1 2 3 4 5 Helpful