Narrow By
  1. Your SelectionAll

Technical Characteristics - FAQs

FAQ Search
Most Recently Published FAQs

Results 71 - 80 of 100

FAQ ID Description
FA166609When using ATS22, what is difference between motor overload alarm and motor overload trip (OLF).
When motor thermal state as calculated by starter is reached to 110%, motor overload alarm is triggered but when motor  thermal state continues to...
FA166608When over sized selection of ATS22 is mandatory. How to do oversize selection.
The Altistart 22 rating is limited to 3.5 IcL. IcL is the nominal current of the Altistart 22. If the application requires a higher rated starting...
FA166607What does “tBS” mean in case of ATS22 or ATS48 soft-starter. Does it indicate fault state of soft-starter.
 “tBS” does not indicate any fault state of soft-starter but as it name suggests it is “Time before re-starting”. It can be set in unit of seconds....
FA166606What minimum power of motor could be operated with ATS22 soft starter.
ATS22 is having inbuilt bypass contactor and its switching takes place only when Imotor (Actual Motor current) of In (Motor rated current set with...
FA166604Are Zx-function keys multifunctional.
Normally, Zx function Keys work as navigation keys. They can also be used in a control diagram while developing logic with zeliosoft2. In this configuration,...
FA166565What cables to be used to connect Local PC to SoMachine software.
TCS XCNA MUM3P:This USB cable is suitable for short duration connection like quick updates or retrieving data values.   BMX XCA USBH045: Grounded...
FA166521Pinout details of Modbus junction box- VW3A8306TF**.
Pinout details of Modbus junction box- VW3A8306TF** is as below,
FA166508Is it mandatory to use heatsink and thermal interface with SSR P range of SSR (Solid State Relays).
SSR P (Panel mounting type SSR) are not with inbuilt heatsink compare to the integrated heat-sink of SSR D (Din rail mounting type SSR) rerlays.   It...
FA166507What is timeout error while communicating with PM1000 & DM6000 meter and what are the reasons for this error.
When a master like EGX, ION Enterprise ,System (PC) sends a query & doesn't receive any response from the Meter  within the wait time then the error...
FA166505For PM1000 meters, when are external CTs and/or PTs required.
External CT is required when the load current to be measured is greater than 6A.   An external PT is required when input voltage greater than 480V

Results 71 - 80 of 100