| FA170616 | Is it possible to operate or configure ATV303 drive with remote HMI
Yes, it is possible to operate and / or to configure ATV303 drive by means of remote HMI Part reference VW3A1006.
|
| FA170611 | Does “dIS” on display of lexium servo drive indicates fault. How to overcome it. “dIS” on display does not indicate fault state of lexium servo drive but it is one of the states of servo drive.
dIS stands for Switch ON Disabled.... |
| FA170610 | When Lexium 32 range of servo drive goes into the “QUICK STOP”. Lexium 32 range of servo drive goes into the QUICK STOP under two conditions
If servo drive meet with an error of class 1 or class 2.
Upon... |
| FA170609 | In Lexium range drive the permissible range of motor shaft movement if absolute position is to be retained while servo drive is powered off. Permissible range of motor shaft movement is +/ - 0.25 revolution from the position at which motor shaft position was
at the moment servo drive was... |
| FA170608 | In Altivar range of drives ,display of current (A) is blinking on 7 –segment LED display. What does this mean. Blinking of Current (A) displayed on 7-segment LED display indicates that drive has reached to the current limitation.
This occurs when current drawn... |
| FA170509 | Where is the Test Button resistor connected between the poles of Vigi iC60 devices (3P and 4P). The Test Button resistor is connected between the poles 2 and 3 of Vigi iC60 devices (3P and 4P).
Please refer the below diagram
|
| FA170508 | What is the earth fault loop impedance values (Zs) for the Acti9 iC60 MCB’s. The earth fault loop impedance values for Acti9 iC60 are given in below table.
|
| FA170507 | How many stop bits does the EGX support.
All EGX devices use an 11-bit frame serial frame. 1 start-bit, 8 data-bits, and 1 or 2 stop bits
depending on the parity selection.
Even parity:... |
| FA170506 | Is it possible to enable "Auto Scrolling" for the EM6400 series meter display. Auto Scroll allows the user to monitor a group of Display Pages sequentially, every 5 seconds, without constant key pressing.
There are three different... |
| FA170505 | Is there any difference in CT wiring of PM800 and PM200/PM700 for Three-Phase 3-wire Power Systems when using 2 CTs. For 3-wire, three-phase systems with 2 CTs, its required to connect terminal S2 = X2 of CT1 to the I2+ terminal of
the PM200/PM700 instead of the... |