FAQs

FAQ Search
Most Recently Published FAQs

Results 11 - 20 of 100

FAQ ID Description
FA170616Is it possible to operate or configure ATV303 drive with remote HMI
Yes, it is possible to operate and / or to configure ATV303 drive by means of remote HMI Part reference VW3A1006.
FA170611Does “dIS” on display of lexium servo drive indicates fault. How to overcome it.
“dIS” on display does not indicate fault state of lexium servo drive but it is one of the states of servo drive. dIS stands for Switch ON Disabled....
FA170610When Lexium 32 range of servo drive goes into the “QUICK STOP”.
Lexium 32 range of servo drive goes into the QUICK STOP under two conditions If servo drive meet with an error of class 1 or class 2. Upon...
FA170609In Lexium range drive the permissible range of motor shaft movement if absolute position is to be retained while servo drive is powered off.
Permissible range of motor shaft movement is +/ - 0.25 revolution from the position at which motor shaft position was at the moment servo drive was...
FA170608In Altivar range of drives ,display of current (A) is blinking on 7 –segment LED display. What does this mean.
Blinking of Current (A) displayed on 7-segment LED display indicates that drive has reached to the current limitation. This occurs when current drawn...
FA170509Where is the Test Button resistor connected between the poles of Vigi iC60 devices (3P and 4P).
The Test Button resistor is connected between the poles 2 and 3 of Vigi iC60 devices (3P and 4P).   Please refer the below diagram
FA170508What is the earth fault loop impedance values (Zs) for the Acti9 iC60 MCB’s.
The earth fault loop impedance values for Acti9 iC60 are given in below table.
FA170507How many stop bits does the EGX support.
All EGX devices use an 11-bit frame serial frame. 1 start-bit, 8 data-bits, and 1 or 2 stop bits depending on the parity selection.   Even parity:...
FA170506Is it possible to enable "Auto Scrolling" for the EM6400 series meter display.
Auto Scroll allows the user to monitor a group of Display Pages sequentially, every 5 seconds, without constant key pressing.   There are three different...
FA170505Is there any difference in CT wiring of PM800 and PM200/PM700 for Three-Phase 3-wire Power Systems when using 2 CTs.
For 3-wire, three-phase systems with 2 CTs, its required to connect terminal S2 = X2 of CT1 to the I2+ terminal of the PM200/PM700 instead of the...

Results 11 - 20 of 100