Can i use 140NOE77100 or 140CRP31200 for synchronizing PLC time with NTP server.

140NOE77100 or 140CRP31200 modules can not sync PLC time with NTP server. You have to use 140NOE77111 or 140NOC78*** modules for synchronization of PLC time with NTP server connected to some other module on the PLC rack.