What is the maximum simultaneous Modbus TCP connections on its server path supported for BMENOC0301 modules.

M580 BMENOC0301 modules supports maximum of 64 simultaneous Modbus TCP connections on its server path considered the NOC firmware should be maintained on v 2.08 or higher else it will only support maximum 32 server connections.