How we can make a switchover between redundant 140CRA31908 modules using application logic.
You can use system bit %S88 to reassign the master of the I/O points. When %S88 is set, the system triggers a 140CRA31908 switch over and assigns...
Can we Hot Swap the SFP transceiver of M580 HSBY CPU.
Do not Hot Swap the SFP transceiver. Insert or remove the transceiver only when there is no power to the CPU.    Failure to follow these instructions...
What is the difference between implicit and Explicit messaging objects for BMXEAE0300 communication.
Below are the differentiation between implicit and Explicit messaging :   Implicit Exchange Objects: These objects are automatically exchanged on...
What is the minimum Firmware Requirement to support IP forwarding service with BMENOP0300 module.
The IP forwarding service is supported by the following versions:    BMENOP0300 firmware version ≥ V2.0  Modicon IEC 61850 Configuration Tool ≥ V3.0 ...
We are not getting option of PMEPXM0100 module in unity Pro v 13.
PMEPXM0100 module is supported with Ecostruxure Control Expert v14 onwards. Thats why module option is not available under Hardware catalog in Unity...
How we can Automatically block service port on M580 Standby CPU in Ecostruxure control Expert Software.
To help avoid creating an unintentional loop caused by connection to the service port, select the Automatic blocking of service port on Standby CPU...
What is the benefit of enabling "Automatic blocking of service port on Standby CPU" in M580 HSBY CPU.
Enabling "Automatic blocking of service port on Standby CPU " Automatically blocks the service port to help avoid an unintentional loop.    NOTE:...
Is it necessary to enable NTP service if M580 safety I/O modules installed in an RIO drop.
Is it necessary to enable NTP service if M580 safety I/O modules installed in an RIO drop.   If you are installing M580 safety I/O modules in an RIO...
How Communications between the M580 safety PAC and safety I/O modules installed in an RIO drop will be done.
Communications between the safety PAC and safety I/O modules installed in an RIO drop are made through an adapter module installed on the RIO drop,...
What is the maximum dissipated power for BMXSDI1602.
The maximum dissipated power for BMXSDI1602 is 3.57W .