India
Welcome to the Schneider Electric Website

Welcome to our website.

You can choose another country to view available products or go to our Global website for company information.

Select your location
View all RED
18687 Product picture Schneider Electric

18687

18687 Product picture Schneider Electric
18687

RCCB with re-closer - RED - 2 poles - 25 A - class A - 30 mA

Show more characteristics >
Add to My Products Remove from My Products
The maximum number of products that can be compared is 4

  • Main
    range of product
    Acti 9
    product or component type
    Residual current circuit breaker (RCCB)
    device short name
    REDs
    protection type
    Recloser
    poles description
    2P
    neutral position
    Left
    signal contacts composition
    1NO or 1NC or intermittent 1 Hz
    [In] rated current
    25 A
    earthing system
    TN-S
    TT
    network type
    AC
    earth-leakage sensitivity
    30 mA
    Complementary
    device location in system
    Outgoer
    network frequency
    50 Hz
    [Ue] rated operational voltage
    230 V AC 50 Hz phase to neutral
    reset
    Fault reset earth leakage
    test function
    Manual at 100 V
    earth-leakage protection time delay
    Instantaneous
    earth-leakage protection class
    Type A
    minimum leakage resistance
    16 kOhm at operating
    8 kOhm at non-operating
    [Im] rated making and breaking capacity
    Idm 630 A 230 V
    rated conditional short-circuit current
    Inc: 6 kA - associated with DPN, 40 A
    Inc: 10 kA - associated with DPNN, 40 A
    Inc: 10 kA - associated with iC60N, 25 A
    Inc: 10 kA - associated with iC60H, 25 A
    Inc: 10 kA - associated with iC60L, 25 A
    Inc: 10 kA - associated with NG125, 25 A
    Inc: 10 kA - associated with gG fuse, 25 A
    [Ui] rated insulation voltage
    500 V
    [Uimp] rated impulse withstand voltage
    4 kV
    control type
    Toggle
    local signalling
    2 LEDs
    Residual current device : ON/OFF indication
    Recloser : ON/OFF indication
    operating mode
    Reclosing time: < 90 s
    Max nb of consecutive restart: 3
    Min interval between 2 closings: 180 s
    Stopping restart cycle if insulation fault present
    Insulation fault presence monitoring
    signalling circuit voltage
    AC: 5...230 V
    DC: 5...230 V
    signalling output current
    0.6 mA min
    100 mA max, cos phi =1
    mounting mode
    Fixed
    mounting support
    35 mm symmetrical DIN rail
    9 mm pitches
    8
    height
    115 mm
    width
    71 mm
    depth
    79.5 mm
    net weight
    0.36 kg
    mechanical durability
    1000 cycles open-close
    connections - terminals
    Guard tunnel terminal35 mm² rigid
    Guard tunnel terminal35 mm² flexible
    Guard tunnel terminal35 mm² flexible with ferrule
    auxiliary connection terminal
    Tunnel type terminal in 2.5 mm² flexible
    Tunnel type terminal in 2.5 mm² rigid
    Tunnel type terminal in 2.5 mm² flexible with ferrule
    wire stripping length
    Power circuit: 12 mm
    Signaling: 9 mm
    tightening torque
    Power circuit: 2 N.m
    Signaling: 0.4 N.m
    Environment
    standards
    EN 61008
    IEC 61008
    IP degree of protection
    IP20
    electromagnetic compatibility
    8/20 µs wave immunity, 250 A
    tropicalisation
    2
    relative humidity
    95 % at 55 °C
    ambient air temperature for operation
    -5…40 °C
    ambient air temperature for storage
    -20…60 °C
    Offer Sustainability
    REACh Regulation
    REACh free of SVHC
    Yes
    EU RoHS Directive
    Mercury free
    Yes
    RoHS exemption information
    China RoHS Regulation
    China RoHS declaration
    Product out of China RoHS scope. Substance declaration for your information
    Circularity Profile
    No need of specific recycling operations
    WEEE
    The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins
    Contractual warranty
    Warranty
    18 months
  • Documents & Downloads

    Language
    • English
    • Spanish
    • French
    • Italian
    Certificate
    Date
    Size
    Add to My Documents
    License IMQ for RED-REDs Automatic Reclosing Device according to EN50557:2011 (Version 1.0)
    Instruction sheet
    Date
    Size
    Add to My Documents
    REDs Recloser Earth leakage Device 2P 25...63 A with 1 auxiliary contact - Instruction Sheet (Version 02)
    REDs Recloser Earth leakage Device 2P 25..63 A with 1 auxiliary contact (Version 02)
    Declaration of conformity
    Date
    Size
    Add to My Documents
    EU Declaration FD16042501C for RCCB + Automatic Recloser Device RED, REDs and REDTest (Version 4.0)
    EU RoHS Declaration
    Date
    Size
    Add to My Documents
    Date 19/9/19
    Size 195.3 KB
    REACh Declaration
    Date
    Size
    Add to My Documents
    Date 19/9/19
    Size 195.3 KB
    RoHs China Declaration
    Date
    Size
    Add to My Documents
    Date 19/9/19
    Size 195.3 KB
  • Technical FAQs

    No results found.
    Unfortunately, related FAQs are unavailable due to temporary technical issues. Please try again later.
Compare products: /