Welcome to the Schneider Electric Website

Welcome to our website.

You can choose another country to view available products or go to our Global website for company information.

Choose another country or region

19060 Product picture Schneider Electric

View all Optional auxiliaries for NG125

Optional auxiliaries for NG125 - 19060

Electrical auxiliaries

19060 Product picture Schneider Electric
View all Optional auxiliaries for NG125

Optional auxiliaries for NG125 - 19060

Electrical auxiliaries

voltage release - MXV - 110..240 V AC

Show more characteristics >
Add to My Products Remove from My Products

  • Main
    range
    Acti 9
    product or component type
    Shunt trip release
    device short name
    MXV
    [Uc] control circuit voltage
    110 V DC
    110...240 V AC 50/60 Hz
    9 mm pitches
    3
    product compatibility
    NG125
    Complementary
    range compatibility
    Acti 9 Vigi NG125
    Acti 9: Acti 9 NG125LMA
    Acti 9: Acti 9 NG125NA
    Acti 9: Acti 9 NG125
    [Ui] rated insulation voltage
    690 V AC 50/60 Hz conforming to EN/IEC 60947-5-1
    [Uimp] rated impulse withstand voltage
    8 kV conforming to EN/IEC 60947-5-1
    local signalling
    Action indicator
    mounting mode
    Fixed
    mounting support
    35 mm symmetrical DIN rail
    height
    106 mm
    width
    25 mm
    depth
    80 mm
    product weight
    0.038 kg
    electrical durability
    10000 cycles conforming to EN/IEC 60947-5-1
    connections - terminals
    Plate terminal 2 cable(s) 2.5 mm² flexible
    Plate terminal 2 cable(s) 2.5 mm² rigid
    Plate terminal 1 cable(s) 0.5...2.5 mm² rigid
    Plate terminal 1 cable(s) 0.5...1.5 mm² flexible
    Plate terminal 1 cable(s) 0.5...1.5 mm² flexible with ferrule
    Plate terminal 2 cable(s) 1.5 mm² flexible with ferrule
    wire stripping length
    10 mm
    tightening torque
    1 N.m
    Environment
    standards
    EN/IEC 60947-5-1
    product certifications
    ASEFA
    ASTA
    KEMA
    LCIE
    IP degree of protection
    IP20 B conforming to EN/IEC 60947-5-1
    IP4 conforming to EN/IEC 60947-5-1
    pollution degree
    3 conforming to EN/IEC 60947-5-1
    overvoltage category
    II
    tropicalisation
    2 conforming to EN/IEC 60947-5-1
    relative humidity
    95 % at 55 °C
    ambient air temperature for operation
    -25...60 °C
    ambient air temperature for storage
    -40...85 °C
    Contractual warranty
    Warranty period
    18 months 18 months
  • Documents & Downloads

    Language
    • English
    User guide
    Date
    Size
    Add to My Documents
    Date 18/3/13
    Size 203.3 KB
    CAD
    Date
    Size
    Add to My Documents
    MXV FOR VIGI NG125
    Date 13/8/13
    Size 613.5 KB
    Date 13/8/13
    Size 928.8 KB
    End of life manual
    Date
    Size
    Add to My Documents
    Date 2/11/17
    Size 227.4 KB
    Product environmental
    Date
    Size
    Add to My Documents
    Date 2/11/17
    Size 168.4 KB
  • Technical FAQs

    No results found.