  • Main
    range of product
    Altivar Easy 310
    product or component type
    Variable speed drive
    product specific application
    Simple machine
    assembly style
    With heat sink
    device short name
    ATV310
    network number of phases
    Three phase
    [Us] rated supply voltage
    380...460 V (- 15...10 %)
    motor power kW
    7.5 kW
    motor power hp
    10 hp
    noise level
    50 dB
    Complementary
    product destination
    Asynchronous motors
    quantity per set
    Set of 1
    EMC filter
    Without EMC filter
    type of cooling
    Integrated fan
    supply frequency
    50/60 Hz +/- 5 %
    communication port protocol
    Modbus
    connector type
    RJ45 for Modbus on front face
    physical interface
    2-wire RS 485 for Modbus
    transmission frame
    RTU for Modbus
    transmission rate
    4800 bit/s
    9600 bit/s
    19200 bit/s
    38400 bit/s
    number of addresses
    1...247 addresses for Modbus
    communication service
    Read holding registers (03), messaging: 29 words
    Write single register (06), messaging: 29 words
    Write multiple registers (16), messaging: 27 words
    Read/write multiple registers (23), messaging: 4/4 words
    Read device identification (43)
    line current
    22.4 A
    apparent power
    17.8 kVA
    prospective line Isc
    <= 5 kA
    continuous output current
    17 A at 4 kHz
    maximum transient current
    25.5 A for 60 s
    power dissipation in W
    203.87 W at In
    speed drive output frequency
    0.5...400 Hz
    nominal switching frequency
    4 kHz
    switching frequency
    2...12 kHz (adjustable)
    speed range
    1...20
    transient overtorque
    170...200 % of nominal motor torque depending on drive rating and type of motor
    braking torque
    Up to 150 % of nominal motor torque with braking resistor at high inertia
    Up to 70 % of nominal motor torque without braking resistor
    asynchronous motor control profile
    Energy saving ratio
    Quadratic voltage/frequency ratio
    Sensorless flux vector control
    motor slip compensation
    Adjustable
    Preset in factory
    output voltage
    380...460 V three phase
    electrical connection
    6...10 mm² at terminal L1, L2, L3, PA/+, PB, U, V, W
    tightening torque
    2.2...2.4 N.m
    insulation
    Electrical between power and control
    supply
    Internal supply for reference potentiometer : 5 V (4.75...5.25 V) DC 10 mA with overload and short-circuit protection
    Internal supply for logic inputs : 24 V (20.4...28.8 V) DC 100 mA with overload and short-circuit protection
    analogue input number
    1
    analogue input type
    Configurable current (AI1) 0...20 mA, impedance 250 Ohm
    Configurable voltage (AI1) 0...10 V, impedance 30 kOhm
    Configurable voltage (AI1) 0...5 V, impedance 30 kOhm
    discrete input number
    4
    discrete input type
    24 V (18...30 V) programmable, at LI1...LI4 terminal(s)
    discrete input logic
    Positive logic (source), 0...< 5 V (state 0), > 11 V (state 1)
    Negative logic (sink), > 16 V (state 0), < 10 V (state 1), input impedance 3.5 kOhm
    sampling duration
    10 ms for analogue input
    20 ms, tolerance +/- 1 ms for logic input
    linearity error
    +/- 0.3 % of maximum value for analogue input
    analogue output number
    1
    analogue output type
    AO1 software-configurable voltage : 0...10 V, impedance: 470 Ohm, resolution 8 bits
    AO1 software-configurable current : 0...20 mA, impedance: 800 Ohm, resolution 8 bits
    discrete output number
    2
    discrete output type
    (LO+, LO-) logic output
    (R1A, R1B, R1C) protected relay output 1 C/O
    minimum switching current
    5 mA at 24 V DC for logic relay
    maximum switching current
    2 A at 250 V AC on inductive load (cos phi = 0.4 L/R = 7 ms) for logic relay
    2 A at 30 V DC on inductive load (cos phi = 0.4 L/R = 7 ms) for logic relay
    3 A at 250 V AC on resistive load (cos phi = 1 L/R = 0 ms) for logic relay
    4 A at 30 V DC on resistive load (cos phi = 1 L/R = 0 ms) for logic relay
    acceleration and deceleration ramps
    S
    U
    Linear from 0...999.9 s
    braking to standstill
    By DC injection, <= 30 s
    protection type
    Against input phase loss in three-phase
    Thermal motor protection via the drive by continuous calculation of I²t
    Line supply overvoltage
    Line supply undervoltage
    Overcurrent between output phases and earth
    Overheating protection
    Short-circuit between motor phases
    frequency resolution
    Converter A/D, 10 bits for analog input
    0.1 Hz for display unit
    time constant
    20 ms, tolerance +/- 1 ms for reference change
    operating position
    Vertical +/- 10 degree
    height
    171 mm
    width
    150 mm
    depth
    232 mm
    product weight
    3.7 kg
    Environment
    electromagnetic compatibility
    Voltage dips and interruptions immunity test conforming to EN/IEC 61000-4-11
    Electrical fast transient/burst immunity test (test level: level 4) conforming to EN/IEC 61000-4-4
    Electrostatic discharge immunity test (test level: level 3) conforming to EN/IEC 61000-4-2
    Immunity to conducted disturbances (test level: level 3) conforming to EN/IEC 61000-4-6
    Radiated radio-frequency electromagnetic field immunity test (test level: level 3) conforming to EN/IEC 61000-4-3
    Surge immunity test (test level: level 3) conforming to EN/IEC 61000-4-5
    standards
    EN/IEC 61800-3
    EN/IEC 61800-5-1
    IP degree of protection
    IP41 on top
    IP20 without blanking plate on upper part
    pollution degree
    2 conforming to EN/IEC 61800-5-1
    environmental characteristic
    Chemical pollution resistance class 3C3 conforming to EN/IEC 60721-3-3
    Dust pollution resistance class 3S2 conforming to EN/IEC 60721-3-3
    shock resistance
    15 gn (duration = 11 ms) conforming to EN/IEC 60068-2-27
    relative humidity
    5...95 % (without condensation) conforming to IEC 60068-2-3
    5...95 % (without dripping water) conforming to IEC 60068-2-3
    ambient air temperature for storage
    -25...70 °C
    ambient air temperature for operation
    -10...55 °C without derating
    55...60 °C protective cover from the top of the drive removed with current derating 2.2 % per °C
    operating altitude
    <= 1000 m without derating
  • Documents & Downloads

    Language
    • English
    Catalogue
    Date
    Size
    Add to My Documents
    Date 12/9/17
    Size 1.7 MB
    User guide
    Date
    Size
    Add to My Documents
    Date 12/10/18
    Size 263.5 KB
    Date 14/1/15
    Size 638.1 KB
    Date 17/3/16
    Size 1.1 MB
    Date 14/3/17
    Size 469.1 KB
    Date 19/10/18
    Size 7.8 MB
    Certificate
    Date
    Size
    Add to My Documents
    Date 28/9/18
    Size 690.6 KB
    Instruction sheet
    Date
    Size
    Add to My Documents
    Date 25/7/18
    Size 5.4 MB
    Product environmental
    Date
    Size
    Add to My Documents
    Date 27/3/18
    Size 1.1 MB
  • Technical FAQs

    No results found.
    Unfortunately, related FAQs are unavailable due to temporary technical issues. Please try again later.
  • Dimensions Drawings

    Dimensions


    Dimensions in mm

    a

    b

    c

    G

    H

    H1

    Ø

    For screws

    150

    220

    171

    130

    210

    232

    5

    M4

    Dimensions in in.

    a

    b

    c

    G

    H

    H1

    Ø

    For screws

    5.91

    8.66

    6.73

    5.12

    8.27

    9.13

    0.20

    M4


  • Mounting and Clearance

    Mounting Recommendations
    Clearance


    Mounting Types

    Mounting Type A


    Mounting Type B


    Remove the protective cover from the top of the drive.


  • Connections and Schema

    Three-Phase Power Supply Wiring Diagram


    A1 :
    Drive
    KM1 :
    Contactor (only if a control circuit is needed)
    P1 :
    2.2 kΩ reference potentiometer. This can be replaced by a 10 kΩ potentiometer (maximum).
    Q1 :
    Circuit breaker
    R :
    Braking resistor (optional)
    (1)
    Negative logic (Sink)
    (2)
    Positive logic (Source) (factory set configuration)
    (3)
    0...10 V or 0...20 mA
    (4)
    Line choke three-phase (optional)