TeSys F reversing contactor - 3P(3 NO) AC-3 <= 440 V 115 A 220 V AC 40...400 Hz

Show more characteristics >
Add to My Products Remove from My Products

  • Main
    range
    TeSys
    product name
    TeSys F
    product or component type
    Reversing contactor
    device short name
    LC2F
    contactor application
    Motor control
    Resistive load
    utilisation category
    AC-1
    AC-3
    device presentation
    Preassembled with reversing power busbar
    poles description
    3P
    power pole contact composition
    3 NO
    [Ue] rated operational voltage
    <= 1000 V AC 50/60 Hz
    <= 460 V DC
    [Ie] rated operational current
    200 A (<= 40 °C) at <= 440 V AC AC-1
    115 A (<= 40 °C) at <= 440 V AC AC-3
    motor power kW
    30 kW at 220...240 V AC 50/60 Hz
    80 kW at 660…690 V AC 50/60 Hz
    55 kW at 380...400 V AC 50/60 Hz
    59 kW at 415 V AC 50/60 Hz
    59 kW at 440 V AC 50/60 Hz
    65 kW at 1000 V AC 50/60 Hz
    75 kW at 500 V AC 50/60 Hz
    control circuit type
    AC 40...400 Hz
    [Uc] control circuit voltage
    220 V AC 40...400 Hz
    [Uimp] rated impulse withstand voltage
    8 kV
    overvoltage category
    III
    [Ith] conventional free air thermal current
    200 A at <= 40 °C
    Irms rated making capacity
    1150 A AC conforming to IEC 60947-4-1
    rated breaking capacity
    920 A conforming to IEC 60947-4-1
    [Icw] rated short-time withstand current
    1100 A <= 40 °C 10 s
    640 A <= 40 °C 30 s
    520 A <= 40 °C 1 min
    400 A <= 40 °C 3 min
    320 A <= 40 °C 10 min
    associated fuse rating
    125 A aM at <= 440 V
    200 A gG at <= 440 V
    average impedance
    0.37 mOhm at 50 Hz - Ith 200 A
    [Ui] rated insulation voltage
    1000 V conforming to IEC 60947-4-1
    1500 V conforming to VDE 0110 group C
    power dissipation per pole
    5 W : AC-3
    interlocking type
    Mechanical
    mounting support
    Plate
    standards
    EN 60947-1
    EN 60947-4-1
    IEC 60947-1
    IEC 60947-4-1
    JIS C8201-4-1
    product certifications
    ABS
    CCC
    CSA
    DNV
    LROS (Lloyds register of shipping)
    RINA
    RMRoS
    UL
    CB
    connections - terminals
    Control circuit : screw clamp terminals 2 cable(s) 1...2.5 mm² - cable stiffness: flexible - with cable end
    Power circuit : connector 1 cable(s) 95 mm²
    Control circuit : screw clamp terminals 1 cable(s) 1...4 mm² - cable stiffness: flexible - without cable end
    Control circuit : screw clamp terminals 2 cable(s) 1...4 mm² - cable stiffness: flexible - without cable end
    Control circuit : screw clamp terminals 1 cable(s) 1...4 mm² - cable stiffness: flexible - with cable end
    Control circuit : screw clamp terminals 1 cable(s) 1...4 mm² - cable stiffness: solid - without cable end
    Control circuit : screw clamp terminals 2 cable(s) 1...4 mm² - cable stiffness: solid - without cable end
    Power circuit : lugs-ring terminals 1 cable(s) 95 mm²
    Power circuit : bar 2 x ( 20 x 3 mm)
    tightening torque
    Control circuit : 1.2 N.m
    Power circuit : 10 N.m
    operating time
    23...35 ms closing
    5...15 ms opening
    mechanical durability
    10 Mcycles
    operating rate
    2400 cyc/h at <= 55 °C
    Complementary
    control circuit voltage limits
    0.35...0.55 Uc at 55 °C drop-out 50/60 Hz
    0.85...1.1 Uc at 55 °C operational 50/60 Hz
    inrush power in VA
    550 VA at 20 °C (cos ϕ 0.3) 50 Hz
    660 VA at 20 °C (cos ϕ 0.3) 60 Hz
    hold-in power consumption in VA
    45 VA at 20 °C (cos ϕ 0.3) 50 Hz
    55 VA at 20 °C (cos ϕ 0.3) 60 Hz
    heat dissipation
    12...16 W
    Environment
    IP degree of protection
    IP20 front face with shrouds (ordered separately) conforming to IEC 60529
    IP20 front face with shrouds (ordered separately) conforming to VDE 0106
    protective treatment
    TH
    ambient air temperature for operation
    -5...55 °C
    ambient air temperature for storage
    -60...80 °C
    permissible ambient air temperature around the device
    -40...70 °C
    operating altitude
    3000 m without derating in temperature
    mechanical robustness
    Vibrations contactor closed 6 Gn, 5...300 Hz
    Shocks contactor open 9 Gn for 11 ms
    Vibrations contactor open 2 Gn, 5...300 Hz
    Shocks contactor closed 15 Gn for 11 ms
    height
    162 mm
    width
    345 mm
    depth
    171 mm
    product weight
    6.86 kg
    Offer Sustainability
    Sustainable offer status
    Green Premium product
    RoHS (date code: YYWW)
    REACh
    Product environmental profile
    Product end of life instructions
    Contractual warranty
    Warranty period
    18 months
  • Documents & Downloads

    Language
    • English
    • French
    Brochure
    Date
    Size
    Add to My Documents
    TeSys F 1000 leaflet (Version 1.0)
    Date 27/2/19
    Size 6.1 MB
    Date 27/2/19
    Size 819.5 MB
    Certificate
    Date
    Size
    Add to My Documents
    CCC TeSys F - LC.F115-150, Czech Republic (Version 1.0)
    CB Certificate - LC1F630-780 - Czech republic - according to IEC 60947-4-1 (Version 1.0)
    Declaration of conformity
    Date
    Size
    Add to My Documents
    EU Declaration TeSys F - LC.F115-800 (Version 1.0)
    End of Life Information
    Date
    Size
    Add to My Documents
    End-of-Life Instructions TeSys LC1F185 to LC1F225 (Version 1.0)
    TeSys LC1F185-225 - EoLi (Version 2.0)
    Date 1/12/15
    Size 181.1 KB
    Marine certificate
    Date
    Size
    Add to My Documents
    RINA Marine Certificate TeSys F - LC.F115-780 contactors (Version 1.0)
    DNV-GL Marine Certificate TeSys F - LC.F115-780 contactor (Version 1.0)
    Product Environmental Profile
    Date
    Size
    Add to My Documents
    TeSys contactor LC1F (Version 2.0)
    Date 21/9/17
    Size 197.1 KB
  • Technical FAQs

    No results found.
    Unfortunately, related FAQs are unavailable due to temporary technical issues. Please try again later.