Welcome to the Schneider Electric Website

Welcome to our website.

You can choose another country to view available products or go to our Global website for company information.

Choose another country or region

    METSEEM6400NGRSCL5 Product picture Schneider Electric

    Range: EM6400NG

    Meters

    METSEEM6400NGRSCL5

    METSEEM6400NGRSCL5 Product picture Schneider Electric
    Range: EM6400NG

    Meters

    METSEEM6400NGRSCL5

    Conzerv Power and Energy meter - inst., pulse, RS485, THD, 15th Har, Class 0.5S

    Show more characteristics >
    Add to My Favourites Remove from My Favourites

    • Main
      range
      Conzerv
      product name
      EM6400NG RS-485
      device short name
      Conzerv EM6400NG
      product or component type
      Energy meter
      Complementary
      power quality analysis
      Up to the 15th harmonic
      device application
      Power monitoring
      type of measurement
      Active and reactive power
      Active and reactive energy
      Apparent energy
      Voltage
      Current
      Frequency
      Apparent power
      metering type
      Average voltage Vavg
      Power factor and displacement PF (signed, four quadrant)
      Active, reactive, apparent energy (signed, four quadrant)
      Average current Iavg
      Unbalance current
      Demand current I1, I2, I3
      Demand power P, Q, S
      Active power P, P1, P2, P3
      Apparent power S, S1, S2, S3
      Peak demand power PM, QM, SM
      Calculated neutral current
      Phase currents
      Voltage U21, U32, U13, V1, V2, V3
      Reactive power Q, Q1, Q2, Q3
      Unbalance voltage
      Peak demand currents
      [Us] rated supply voltage
      40...300 V AC 45...65 Hz
      40...300 V DC
      network frequency
      60 Hz
      50 Hz
      [In] rated current
      1 A
      5 A
      poles description
      2P + N
      2P
      1P + N
      3P
      3P + N
      power consumption in VA
      < 6 VA at 277 V AC between phase and neutral
      power consumption in W
      < 2 W at 277 V DC
      display type
      7 segments LED
      display colour
      Red
      messages display capacity
      3 fields of 4 characters
      display digits
      12 digit(s) - 14.2 mm in height
      communication of data
      Reading of time-stamped measurements and events
      Total energy
      Net energy
      Energy metering
      tamperproof of settings
      Protected by access code
      sampling rate
      64 samples/cycle
      measurement current
      5...6000 mA
      analogue input type
      Current 0...12 A (impedance 0.3 MOhm) 6 terminal(s)
      Voltage (impedance 5 MOhm) 4 terminal(s)
      measurement voltage
      35...480 V AC 45...65 Hz between phases
      35...277 V AC 45...65 Hz between phase and neutral
      35...600 V AC 45...65 Hz between phases
      35...347 V AC 45...65 Hz between phase and neutral
      600...999000 V AC 45...65 Hz with external VT
      frequency measurement range
      45...65 Hz
      measurement accuracy
      +/- 0.05 % frequency
      +/- 0.5 % current
      +/- 0.5 % voltage
      +/- 0.5 % power
      +/- 0.01 power factor
      accuracy class
      Class 2 (reactive energy according to IEC 62053-23)
      Class 1 (active energy according to IEC 62053-21)
      Class 5P (harmonic distorsion (I THD & U THD) according to IEC 61557-12)
      Class 5P (individual harmonics up to the 15th according to IEC 61557-12)
      number of outputs
      0
      refresh time
      Configurable from 1 to 60 min
      information displayed
      Voltage min/max
      Current min/max
      Power factor min/max
      Frequency min/max
      Active power min/max
      Apparent power min/max
      Reactive power min/max
      Time min/max
      Demand current past value
      Demand current present value
      Demand power past value
      Demand power present value
      local signalling
      Green LED : activity
      Green LED : communication status
      Red LED : output signal
      communication port protocol
      Modbus 2 wires, : 4800 bps, 9600 bps, 19200 bps, 38.4 Kbps, even/odd or none, insulation: 2500 V
      communication port support
      RS485
      data recording
      Min/max of instantaneous values
      Time stamping
      Energy consumption logs
      material
      Polycarbonate
      flame retardance
      V-0 UL 94 conforming to UL 94 V-0
      mounting mode
      Flush-mounted
      Panel-mounted
      mounting support
      Framework
      fixing mode
      By clamp
      installation category
      III
      type of installation
      Indoor installation
      measurement category
      Category III up to <= 480 V
      Category II up to > 480...600 V
      electrical insulation class
      Class II
      connections - terminals
      Current circuit : bottom screw clamp terminals 2.08...3.31 mm²
      Voltage circuit : top screw clamp terminals 0.82...3.31 mm²
      Control circuit : top screw clamp terminals 0.82...3.31 mm²
      Communication : screw clamp terminals 0.33...3.31 mm²
      tightening torque
      Current circuit : 0.9...1 N.m with Philips No 2
      Voltage circuit : 0.9...1 N.m with Philips No 2
      Control circuit : 0.9...1 N.m with Philips No 2
      Communication : 0.9...1 N.m with Philips No 2
      wire stripping length
      Communication : 7 mm
      Current circuit : 3.68 mm
      Voltage circuit : 7 mm
      Control circuit : 7 mm
      standards
      IEC 61010-1 ed. 3
      UL 61010-1 ed. 3
      product certifications
      CE conforming to IEC 61010-1
      CULus conforming to UL 61010-1
      CULus conforming to CSA C22.2 No 61010-1
      C-Tick
      width
      96 mm
      depth
      73 mm panel
      13 mm outside
      height
      96 mm
      product weight
      600 g
      Environment
      electromagnetic compatibility
      ● electrical fast transient/burst immunity test, conforming to IEC 61000-4-4
      ● conducted RF disturbances, conforming to IEC 61000-4-6
      ● radiated radio-frequency electromagnetic field immunity test, conforming to IEC 61000-4-3
      ● voltage dips and interruptions immunity test, conforming to IEC 61000-4-11
      ● electrostatic discharge, conforming to IEC 61000-4-2
      ● surge immunity test, conforming to IEC 61000-4-5
      ● magnetic field at power frequency, conforming to IEC 61000-4-8
      ● emission tests, conforming to FCC part 15 class A
      overvoltage category
      III
      IP degree of protection
      IP30 (body) conforming to IEC 60529
      IP51 (front) conforming to IEC 60529
      relative humidity
      5...95 % 50 °C
      pollution degree
      2
      ambient air temperature for operation
      -10...60 °C
      ambient air temperature for storage
      -20...70 °C
      operating altitude
      <= 2000 m
      service life
      > 7 yr
      Offer Sustainability
      RoHS (date code: YYWW)
      Compliant  - since  1730  -  Schneider Electric declaration of conformity Schneider Electric declaration of conformity
    • Documents & Downloads

      Language
      • English
      Catalogue Page
      Date
      Size
      Add to My Documents
      EM6400NG Multi-function Meter Catalogue Pages
      Declaration of conformity
      Date
      Size
      Add to My Documents
      Date 10/5/16
      Size 648.1 KB
      End of life manual
      Date
      Size
      Add to My Documents
      Date 14/7/18
      Size 411.7 KB
      Product environmental
      Date
      Size
      Add to My Documents
      Date 14/7/18
      Size 440.2 KB
      Technical leaflet
      Date
      Size
      Add to My Documents
      EM6400NG Multi-function Meter Technical Datasheet
    • Technical FAQs

      No results found.
      Unfortunately, related FAQs are unavailable due to temporary technical issues. Please try again later.