    • Main
      range of product
      Modicon M221
      product or component type
      Logic controller
      [Us] rated supply voltage
      100...240 V AC
      discrete input number
      24 discrete input conforming to IEC 61131-2 Type 1
      analogue input number
      2 at input range: 0...10 V
      discrete output type
      Relay normally open
      discrete output number
      16 relay
      discrete output voltage
      5...125 V DC
      5...250 V AC
      discrete output current
      2 A
      Complementary
      discrete I/O number
      40
      number of I/O expansion module
      <= 7 for relay output
      supply voltage limits
      85...264 V
      network frequency
      50/60 Hz
      inrush current
      <= 40 A
      power consumption in VA
      <= 67 VA at 100...240 V with max number of I/O expansion module
      <= 37 VA at 100...240 V without I/O expansion module
      power supply output current
      0.52 A at 5 V for expansion bus
      0.24 A at 24 V for expansion bus
      discrete input logic
      Sink or source (positive/negative)
      discrete input voltage
      24 V
      discrete input voltage type
      DC
      analogue input resolution
      10 bits
      LSB value
      10 mV
      conversion time
      1 ms per channel + 1 controller cycle time for analog input
      permitted overload on inputs
      +/- 30 V DC for analog input with 5 min maximum
      +/- 13 V DC for analog input permanent
      voltage state 1 guaranteed
      >= 15 V for input
      voltage state 0 guaranteed
      <= 5 V for input
      discrete input current
      7 mA for discrete input
      5 mA for fast input
      input impedance
      4.9 kOhm for fast input
      3.4 kOhm for discrete input
      100 kOhm for analog input
      response time
      10 ms turn-on operation for output
      35 µs turn-off operation for input; I2...I5 terminal
      10 ms turn-off operation for output
      5 µs turn-on operation for fast input; I0, I1, I6, I7 terminal
      35 µs turn-on operation for input; other terminals terminal
      5 µs turn-off operation for fast input; I0, I1, I6, I7 terminal
      100 µs turn-off operation for input; other terminals terminal
      configurable filtering time
      0 ms for input
      12 ms for input
      3 ms for input
      output voltage limits
      125 V DC
      277 V AC
      current per output common
      7 A
      absolute accuracy error
      +/- 1 % of full scale for analog input
      electrical durability
      Inductive AC-15, (cos phi = 0.35) 240 V / 120 VA : 100000 cycles
      Resistive DC-12, 24 V / 48 W : 100000 cycles
      Resistive AC-12, 120 V / 240 VA : 100000 cycles
      Inductive AC-15, (cos phi = 0.35) 240 V / 36 VA : 300000 cycles
      Resistive AC-12, 120 V / 80 VA : 300000 cycles
      Inductive (L/R = 7 ms) DC-13, 24 V / 24 W : 100000 cycles
      Resistive DC-12, 24 V / 16 W : 300000 cycles
      Inductive (L/R = 7 ms) DC-13, 24 V / 7.2 W : 300000 cycles
      Inductive AC-14, (cos phi = 0.7) 240 V / 240 VA : 100000 cycles
      Inductive AC-15, (cos phi = 0.35) 120 V / 60 VA : 100000 cycles
      Inductive AC-14, (cos phi = 0.7) 240 V / 72 VA : 300000 cycles
      Inductive AC-15, (cos phi = 0.35) 120 V / 18 VA : 300000 cycles
      Resistive AC-12, 240 V / 480 VA : 100000 cycles
      Inductive AC-14, (cos phi = 0.7) 120 V / 120 VA : 100000 cycles
      Resistive AC-12, 240 V / 160 VA : 300000 cycles
      Inductive AC-14, (cos phi = 0.7) 120 V / 36 VA : 300000 cycles
      switching frequency
      20 switching operations/minute with maximum load
      mechanical durability
      >= 20000000 cycles for relay output
      minimum load
      1 mA at 5 V DC for relay output
      protection type
      Without protection at 5 A
      reset time
      1 s
      memory capacity
      256 kB for user application and data RAM with 10000 instructions
      256 kB for internal variables RAM
      data backed up
      256 kB built-in flash memory for backup of application and data
      data storage equipment
      2 GB SD card optional
      battery type
      BR2032 lithium non-rechargeable, battery life: 4 yr
      backup time
      1 year at 25 °C by interruption of power supply
      execution time for 1 KInstruction
      0.3 ms for event and periodic task
      execution time per instruction
      0.2 µs Boolean
      exct time for event task
      60 µs response time
      maximum size of object areas
      512 %M memory bits
      8000 %MW memory words
      512 %KW constant words
      255 %TM timers
      255 %C counters
      realtime clock
      With
      clock drift
      <= 30 s/month at 25 °C
      regulation loop
      Adjustable PID regulator up to 14 simultaneous loops
      counting input number
      4 fast input (HSC mode) (counting frequency: 100 kHz), counting capacity: 32 bits
      control signal type
      A/B
      Pulse/direction
      Single phase
      integrated connection type
      USB port with connector mini B USB 2.0
      Non isolated serial link "serial 1" with connector RJ45 and interface RS485
      Non isolated serial link "serial 2" with connector RJ45 and interface RS232/RS485
      supply
      Serial serial link supply at 5 V 200 mA
      transmission rate
      1.2...115.2 kbit/s (115.2 kbit/s by default) for bus length of 15 m - communication protocol: RS485
      1.2...115.2 kbit/s (115.2 kbit/s by default) for bus length of 3 m - communication protocol: RS232
      480 Mbit/s - communication protocol: USB
      communication port protocol
      USB port : USB protocol - SoMachine-Network
      Non isolated serial link : Modbus protocol master/slave - RTU/ASCII or SoMachine-Network
      local signalling
      1 LED green for SD card access (SD)
      1 LED red for BAT
      1 LED green for SL1
      1 LED green for SL2
      1 LED per channel green for I/O state
      1 LED red for module error (ERR)
      1 LED green for PWR
      1 LED green for RUN
      electrical connection
      Mini B USB 2.0 connector for a programming terminal
      Terminal block, 3 terminal(s) for connecting the 24 V DC power supply
      Connector, 4 terminal(s) for analogue inputs
      Removable screw terminal block for inputs
      Removable screw terminal block for outputs
      cable distance between devices
      Shielded cable: 10 m for fast input
      Unshielded cable: 30 m for output
      Unshielded cable: 30 m for digital input
      Unshielded cable: 1 m for analog input
      insulation
      2300 V AC between output and internal logic
      Non-insulated between analogue inputs
      500 V AC between input and internal logic
      Non-insulated between analogue input and internal logic
      1500 V AC between supply and ground
      500 V AC between sensor power supply and ground
      500 V AC between input and ground
      1500 V AC between output and ground
      2300 V AC between supply and internal logic
      500 V AC between sensor power supply and internal logic
      500 V AC between Ethernet terminal and internal logic
      2300 V AC between supply and sensor power supply
      marking
      CE
      sensor power supply
      24 V DC at 250 mA supplied by the controller
      mounting support
      Top hat type TH35-15 rail conforming to IEC 60715
      Top hat type TH35-7.5 rail conforming to IEC 60715
      Plate or panel with fixing kit
      height
      90 mm
      depth
      70 mm
      width
      160 mm
      product weight
      0.456 kg
      Environment
      standards
      EN/IEC 60664-1
      EN/IEC 61131-2
      EN/IEC 61010-2-201
      product certifications
      ABS
      CSA
      cULus
      LR
      IACS E10
      RCM
      EAC
      DNV-GL
      environmental characteristic
      Ordinary and hazardous location
      resistance to electrostatic discharge
      4 kV on contact conforming to EN/IEC 61000-4-2
      8 kV in air conforming to EN/IEC 61000-4-2
      resistance to electromagnetic fields
      10 V/m ( 80 MHz...1 GHz) conforming to EN/IEC 61000-4-3
      3 V/m ( 1.4 GHz...2 GHz) conforming to EN/IEC 61000-4-3
      1 V/m ( 2...2.7 GHz) conforming to EN/IEC 61000-4-3
      resistance to magnetic fields
      30 A/m 50/60 Hz conforming to EN/IEC 61000-4-8
      resistance to fast transients
      2 kV for power lines conforming to EN/IEC 61000-4-4
      2 kV for relay output conforming to EN/IEC 61000-4-4
      1 kV for Ethernet line conforming to EN/IEC 61000-4-4
      1 kV for serial link conforming to EN/IEC 61000-4-4
      1 kV for I/O conforming to EN/IEC 61000-4-4
      surge withstand
      2 kV for power lines (AC) in common mode conforming to EN/IEC 61000-4-5
      2 kV for relay output in common mode conforming to EN/IEC 61000-4-5
      1 kV for I/O in common mode conforming to EN/IEC 61000-4-5
      1 kV for shielded cable in common mode conforming to EN/IEC 61000-4-5
      0.5 kV for power lines (DC) in differential mode conforming to EN/IEC 61000-4-5
      1 kV for power lines (AC) in differential mode conforming to EN/IEC 61000-4-5
      1 kV for relay output in differential mode conforming to EN/IEC 61000-4-5
      0.5 kV for power lines (DC) in common mode conforming to EN/IEC 61000-4-5
      resistance to conducted disturbances
      10 Vrms (0.15...80 MHz) conforming to EN/IEC 61000-4-6
      3 Vrms (0.1...80 MHz) conforming to Marine specification (LR, ABS, DNV, GL)
      10 Vrms (spot frequency (2, 3, 4, 6.2, 8.2, 12.6, 16.5, 18.8, 22, 25 MHz)) conforming to Marine specification (LR, ABS, DNV, GL)
      electromagnetic emission
      Conducted emissions conforming to EN/IEC 55011 power lines (AC), 0.15...0.5 MHz : 79 dBμV/m QP/66 dBμV/m AV
      Conducted emissions conforming to EN/IEC 55011 power lines (AC), 0.5...300 MHz : 73 dBμV/m QP/60 dBμV/m AV
      Conducted emissions conforming to EN/IEC 55011 power lines, 10...150 kHz : 120...69 dBµV/m QP
      Conducted emissions conforming to EN/IEC 55011 power lines, 1.5...30 MHz : 63 dBμV/m QP
      Radiated emissions conforming to EN/IEC 55011 class A 10 m, 30...230 MHz : 40 dBμV/m QP
      Conducted emissions conforming to EN/IEC 55011 power lines, 150...1500 kHz : 79...63 dBμV/m QP
      Radiated emissions conforming to EN/IEC 55011 class A 10 m, 200...1000 MHz : 47 dBμV/m QP
      immunity to microbreaks
      10 ms
      ambient air temperature for operation
      -10...55 °C for horizontal installation
      -10...35 °C for vertical installation
      ambient air temperature for storage
      -25...70 °C
      relative humidity
      10...95 % without condensation in operation
      10...95 % without condensation in storage
      IP degree of protection
      IP20 with protective cover in place
      pollution degree
      <= 2
      operating altitude
      0...2000 m
      storage altitude
      0...3000 m
      vibration resistance
      3.5 mm (vibration frequency: 5...8.4 Hz) on symmetrical rail
      1 gn (vibration frequency: 8.4...150 Hz) on symmetrical rail
      3.5 mm (vibration frequency: 5...8.4 Hz) on panel mounting
      1 gn (vibration frequency: 8.4...150 Hz) on panel mounting
      shock resistance
      98 m/s² (test wave duration:11 ms)
      Offer Sustainability
      Sustainable offer status
      Green Premium product
      RoHS (date code: YYWW)
      Compliant  - since  1415  -  Schneider Electric declaration of conformity Schneider Electric declaration of conformity
      REACh
      Product environmental profile
      Product end of life instructions
      Available End of life manual
    • Documents & Downloads

      Language
      • English
      Catalogue
      Date
      Size
      Add to My Documents
      Date 2/5/18
      Size 5.2 MB
      User guide
      Date
      Size
      Add to My Documents
      Date 24/12/15
      Size 1.2 MB
      Date 21/9/17
      Size 585.1 KB
      Date 29/3/18
      Size 4 MB
      Date 1/3/18
      Size 6.9 MB
      Date 20/8/18
      Size 9.1 MB
      CAD
      Date
      Size
      Add to My Documents
      Date 19/10/15
      Size 14 MB
      Instruction sheet
      Date
      Size
      Add to My Documents
      Date 21/9/17
      Size 3.1 MB
      Date 15/11/17
      Size 6.9 MB
      System user guide
      Date
      Size
      Add to My Documents
      Compact Hardwired Logic Controller M221, System User Guide
      Declaration of conformity
      Date
      Size
      Add to My Documents
      Date 3/5/18
      Size 400.7 KB
      Date 23/9/17
      Size 565.5 KB
      End of life manual
      Date
      Size
      Add to My Documents
      Product environmental
      Date
      Size
      Add to My Documents
    • Technical FAQs

      No results found.
      Unfortunately, related FAQs are unavailable due to temporary technical issues. Please try again later.