India
Welcome to the Schneider Electric Website

Welcome to our website.

You can choose another country to view available products or go to our Global website for company information.

Choose another country or region
Add to My Products Remove from My Products

  • Main
    range of product
    Modicon M221
    product or component type
    Logic controller
    [Us] rated supply voltage
    100...240 V AC
    discrete input number
    14, discrete input conforming to IEC 61131-2 Type 1
    analogue input number
    2 at 0...10 V
    discrete output type
    Relay normally open
    discrete output number
    10 relay
    discrete output voltage
    5...125 V DC
    5...250 V AC
    discrete output current
    2 A
    Complementary
    discrete I/O number
    24
    maximum number of I/O expansion module
    7for transistor output
    7for relay output
    supply voltage limits
    85…264 V
    network frequency
    50/60 Hz
    inrush current
    40 A
    maximum power consumption in VA
    58 VA at 100...240 V with max number of I/O expansion module
    35 VA at 100...240 V without I/O expansion module
    power supply output current
    0.52 A 5 Vfor expansion bus
    0.16 A 24 Vfor expansion bus
    discrete input logic
    Sink or source (positive/negative)
    discrete input voltage
    24 V
    discrete input voltage type
    DC
    analogue input resolution
    10 bits
    LSB value
    10 mV
    conversion time
    1 ms per channel + 1 controller cycle time for analogue input analog input
    permitted overload on inputs
    +/- 30 V DCfor 5 min (maximum)for analog input
    +/- 13 V DC (permanent)for analog input
    voltage state 1 guaranteed
    >= 15 Vfor input
    voltage state 0 guaranteed
    <= 5 Vfor input
    discrete input current
    7 mAfor discrete input
    5 mAfor fast input
    input impedance
    3.4 kOhmfor discrete input
    100 kOhmfor analog input
    4.9 kOhmfor fast input
    response time
    35 µs turn-off, I2...I5 terminal(s)for input
    10 ms turn-onfor output
    10 ms turn-offfor output
    5 µs turn-on, I0, I1, I6, I7 terminal(s)for fast input
    35 µs turn-on, other terminals terminal(s)for input
    5 µs turn-off, I0, I1, I6, I7 terminal(s)for fast input
    100 µs turn-off, other terminals terminal(s)for input
    configurable filtering time
    0 msfor input
    3 msfor input
    12 msfor input
    output voltage limits
    125 V DC
    277 V AC
    maximum current per output common
    4 A at COM 2
    7 A at COM 0
    7 A at COM 1
    absolute accuracy error
    +/- 1 % of full scalefor analog input
    electrical durability
    100000 cycles AC-12, 120 V, 240 VA, resistive
    100000 cycles AC-12, 240 V, 480 VA, resistive
    300000 cycles AC-12, 120 V, 80 VA, resistive
    300000 cycles AC-12, 240 V, 160 VA, resistive
    100000 cycles AC-15, cos phi = 0.35, 120 V, 60 VA, inductive
    100000 cycles AC-15, cos phi = 0.35, 240 V, 120 VA, inductive
    300000 cycles AC-15, cos phi = 0.35, 120 V, 18 VA, inductive
    300000 cycles AC-15, cos phi = 0.35, 240 V, 36 VA, inductive
    100000 cycles AC-14, cos phi = 0.7, 120 V, 120 VA, inductive
    100000 cycles AC-14, cos phi = 0.7, 240 V, 240 VA, inductive
    300000 cycles AC-14, cos phi = 0.7, 120 V, 36 VA, inductive
    300000 cycles AC-14, cos phi = 0.7, 240 V, 72 VA, inductive
    100000 cycles DC-12, 24 V, 48 W, resistive
    300000 cycles DC-12, 24 V, 16 W, resistive
    100000 cycles DC-13, 24 V, 24 W, inductive (L/R = 7 ms)
    300000 cycles DC-13, 24 V, 7.2 W, inductive (L/R = 7 ms)
    switching frequency
    20 switching operations/minute with maximum load
    mechanical durability
    20000000 cyclesfor relay output
    minimum load
    1 mA at 5 V DCfor relay output
    protection type
    Without protection at 5 A
    reset time
    1 s
    memory capacity
    256 kBfor user application and data RAM with 10000 instructions
    256 kBfor internal variables RAM
    data backed up
    256 kB built-in flash memoryfor backup of application and data
    data storage equipment
    2 GB SD card (optional)
    battery type
    BR2032 lithium non-rechargeable, battery life: 4 year(s)
    backup time
    1 year at 25 °C (by interruption of power supply)
    execution time for 1 KInstruction
    0.3 msfor event and periodic task
    execution time per instruction
    0.2 µs Boolean
    exct time for event task
    60 µs response time
    maximum size of object areas
    255 %TM timers
    512 %M memory bits
    8000 %MW memory words
    255 %C counters
    512 %KW constant words
    realtime clock
    With
    clock drift
    <= 30 s/month at 25 °C
    regulation loop
    Adjustable PID regulator up to 14 simultaneous loops
    counting input number
    4 fast input (HSC mode) at 100 kHz 32 bits
    counter function
    A/B
    Single phase
    Pulse/direction
    integrated connection type
    USB port with mini B USB 2.0 connector
    Non isolated serial link serial 1 with RJ45 connector and RS232/RS485 interface
    Ethernet with RJ45 connector
    supply
    (serial)serial link supply: 5 V, <200 mA
    transmission rate
    1.2...115.2 kbit/s (115.2 kbit/s by default) for bus length of 15 mfor RS485
    1.2...115.2 kbit/s (115.2 kbit/s by default) for bus length of 3 mfor RS232
    480 Mbit/sfor USB
    communication port protocol
    USB port: USB - SoMachine-Network
    Non isolated serial link: Modbus master/slave - RTU/ASCII or SoMachine-Network
    Ethernet
    port Ethernet
    10BASE-T/100BASE-TX 1 port with 100 m copper cable
    communication service
    Modbus TCP server
    Modbus TCP slave device
    DHCP client
    Modbus TCP client
    Ethernet/IP adapter
    local signalling
    PWR: 1 LED (green)
    RUN: 1 LED (green)
    Module error (ERR): 1 LED (red)
    SD card access (SD): 1 LED (green)
    BAT: 1 LED (red)
    I/O state: 1 LED per channel (green)
    SL: 1 LED (green)
    ACT: Ethernet network activity (green)
    Link (Link Status): Ethernet network link (yellow)
    electrical connection
    removable screw terminal block for inputs
    removable screw terminal block for outputs
    terminal block, 3 terminal(s) for connecting the 24 V DC power supply
    connector, 4 terminal(s) for analogue inputs
    Mini B USB 2.0 connector for a programming terminal
    maximum cable distance between devices
    Shielded cable: <10 mfor fast input
    Unshielded cable: <30 mfor output
    Unshielded cable: <30 mfor digital input
    Unshielded cable: <1 mfor analog input
    insulation
    Between input and internal logic at 500 V AC
    Non-insulated between analogue input and internal logic
    Non-insulated between analogue inputs
    Between supply and ground at 1500 V AC
    Between sensor power supply and ground at 500 V AC
    Between input and ground at 500 V AC
    Between output and ground at 1500 V AC
    Between supply and internal logic at 2300 V AC
    Between sensor power supply and internal logic at 500 V AC
    Between output and internal logic at 2300 V AC
    Between Ethernet terminal and internal logic at 500 V AC
    Between supply and sensor power supply at 2300 V AC
    marking
    CE
    sensor power supply
    24 V DC at 250 mA supplied by the controller
    mounting support
    Top hat type TH35-15 rail conforming to IEC 60715
    Top hat type TH35-7.5 rail conforming to IEC 60715
    plate or panel with fixing kit
    height
    90 mm
    depth
    70 mm
    width
    110 mm
    product weight
    0.395 kg
    Environment
    standards
    EN/IEC 61010-2-201
    EN/IEC 61131-2
    EN/IEC 60664-1
    product certifications
    LR
    CULus
    IACS E10
    CSA
    ABS
    DNV-GL
    EAC
    RCM
    environmental characteristic
    Ordinary and hazardous location
    resistance to electrostatic discharge
    8 kV in air conforming to EN/IEC 61000-4-2
    4 kV on contact conforming to EN/IEC 61000-4-2
    resistance to electromagnetic fields
    10 V/m 80 MHz...1 GHz conforming to EN/IEC 61000-4-3
    3 V/m 1.4 GHz...2 GHz conforming to EN/IEC 61000-4-3
    1 V/m 2...2.7 GHz conforming to EN/IEC 61000-4-3
    resistance to magnetic fields
    30 A/m 50/60 Hz conforming to EN/IEC 61000-4-8
    resistance to fast transients
    2 kV conforming to EN/IEC 61000-4-4 (power lines)
    2 kV conforming to EN/IEC 61000-4-4 (relay output)
    1 kV conforming to EN/IEC 61000-4-4 (I/O)
    1 kV conforming to EN/IEC 61000-4-4 (Ethernet line)
    1 kV conforming to EN/IEC 61000-4-4 (serial link)
    surge withstand
    2 kV power lines (AC) common mode conforming to EN/IEC 61000-4-5
    2 kV relay output common mode conforming to EN/IEC 61000-4-5
    1 kV I/O common mode conforming to EN/IEC 61000-4-5
    1 kV shielded cable common mode conforming to EN/IEC 61000-4-5
    0.5 kV power lines (DC) differential mode conforming to EN/IEC 61000-4-5
    1 kV power lines (AC) differential mode conforming to EN/IEC 61000-4-5
    1 kV relay output differential mode conforming to EN/IEC 61000-4-5
    0.5 kV power lines (DC) common mode conforming to EN/IEC 61000-4-5
    resistance to conducted disturbances
    10 V 0.15...80 MHz conforming to EN/IEC 61000-4-6
    3 V 0.1...80 MHz conforming to Marine specification (LR, ABS, DNV, GL)
    10 V spot frequency (2, 3, 4, 6.2, 8.2, 12.6, 16.5, 18.8, 22, 25 MHz) conforming to Marine specification (LR, ABS, DNV, GL)
    electromagnetic emission
    Conducted emissions - test level: 79 dBμV/m QP/66 dBμV/m AV ( power lines (AC)) at 0.15…0.5 MHz conforming to EN/IEC 55011
    Conducted emissions - test level: 73 dBμV/m QP/60 dBμV/m AV ( power lines (AC)) at 0.5…300 MHz conforming to EN/IEC 55011
    Conducted emissions - test level: 120...69 dBµV/m QP ( power lines) at 10…150 kHz conforming to EN/IEC 55011
    Conducted emissions - test level: 63 dBμV/m QP ( power lines) at 1.5…30 MHz conforming to EN/IEC 55011
    Radiated emissions - test level: 40 dBμV/m QP class A ( 10 m) at 30…230 MHz conforming to EN/IEC 55011
    Conducted emissions - test level: 79...63 dBμV/m QP ( power lines) at 150…1500 kHz conforming to EN/IEC 55011
    Radiated emissions - test level: 47 dBμV/m QP class A ( 10 m) at 200…1000 MHz conforming to EN/IEC 55011
    immunity to microbreaks
    10 ms
    ambient air temperature for operation
    -10…55 °C (horizontal installation)
    -10…35 °C (vertical installation)
    ambient air temperature for storage
    -25…70 °C
    relative humidity
    10…95 %, without condensation (in operation)
    10…95 %, without condensation (in storage)
    IP degree of protection
    IP20 with protective cover in place
    pollution degree
    <= 2
    operating altitude
    0...2000 m
    storage altitude
    0…3000 m
    vibration resistance
    3.5 mm at 5…8.4 Hz on symmetrical rail
    3.5 mm at 5…8.4 Hz on panel mounting
    1 gn at 8.4…150 Hz on symmetrical rail
    1 gn at 8.4…150 Hz on panel mounting
    shock resistance
    98 m/s²for 11 ms
    Offer Sustainability
    Sustainable offer status
    Green Premium product
    REACh Regulation
    EU RoHS Directive
    Environmental Disclosure
    Circularity Profile
  • Documents & Downloads

    Language
    • English
    • Kazakh
    • Spanish
    • Portuguese
    • Russian
    • French
    • Italian
    • German
    • Chinese
    • Turkish
    Catalogue
    Date
    Size
    Add to My Documents
    Modicon M221 logic controllers (Version 7.0)
    User guide
    Date
    Size
    Add to My Documents
    Material Handling - Zero Pressure Accumulation M221, Project Template User Guide (Version 01)
    Modicon TMC2 Cartridges, Programming Guide (Version 01)
    Material Working - Drilling Machine With M221, Project Template User Guide (Version 00)
    Modicon M221 Logic Controller, Hardware Guide (Version 00)
    Modicon M221 Logic Controller, Programming Guide (Version 00)
    Modicon TMC2 Cartridges, Hardware Guide (Version 00)
    Modicon TMC2 Cartridges, Programming Guide (Version 00)
    Modicon M221 - Logic Controller, Programming Guide (Version 09)
    SoMachine Basic - Operating guide (Version 10)
    Modicon TMC2 Cartridges, Hardware Guide (Version 01)
    Modicon M221 Logic Controller, Hardware Guide (Version 06)
    CAD
    Date
    Size
    Add to My Documents
    CAD file (on TraceParts) for TM221CE24R: controller M221 24 IO relay Ethernet (Version 2.0)
    CAD for TM221CE24R: controller M221 24 IO relay Ethernet (Version 1.0)
    Compact Hardwired Logic Controller M221 - Wiring Diagram (Version 1.0)
    Certificate
    Date
    Size
    Add to My Documents
    UL_Modicon_M2xx (Version 1.0)
    Date 10/1/19
    Size 56.1 KB
    UL_Modicon_M2xx_Haz.Loc. (Version 1.0)
    Date 10/1/19
    Size 51.7 KB
    CSA_2684938_Certificate_M221_TM3 (Version 2.0)
    Date 12/9/17
    Size 151.2 KB
    Instruction sheet
    Date
    Size
    Add to My Documents
    Modicon TMC2 - Cartridges, Instruction Sheet (Version 07)
    TM221C..R AC Logic Controller, Instruction sheet (Version 10)
    Declaration of conformity
    Date
    Size
    Add to My Documents
    Modicon DoC TM221 (Version 1.3)
    Date 3/5/18
    Size 400.7 KB
    RCM_SupplierDeclarationOfConformity_TM221_TM3 (Version 1.0)
    End of Life Information
    Date
    Size
    Add to My Documents
    Modicon M221 Bricks controllers, Product End-of-Life Instructions (Version 3.0)
    EU RoHS Declaration
    Date
    Size
    Add to My Documents
    Date 17/4/19
    Size 195.3 KB
    Firmware - Released
    Date
    Size
    Add to My Documents
    M221 Firmware V1.3 SP2 (Version 1.0)
    Date 7/1/16
    Size 1 MB
    Marine certificate
    Date
    Size
    Add to My Documents
    LR Type Approval TM221 and TM3 (Version 1.1)
    Date 23/9/17
    Size 171.3 KB
    ABS PDA TM221 and TM3 (Version 1.1)
    Date 18/10/16
    Size 1.5 MB
    DNV-GL Marine Certificate TM221 PLC (Version 1.1)
    Product Environmental Profile
    Date
    Size
    Add to My Documents
    Modicon M221 Bricks controllers, Product Environmental Profile (Version 3.0)
    REACh Declaration
    Date
    Size
    Add to My Documents
    Date 17/4/19
    Size 195.3 KB
    System user guide
    Date
    Size
    Add to My Documents
    Compact Hardwired Logic Controller M221, System User Guide (Version 00)
  • Technical FAQs

    No results found.
    Unfortunately, related FAQs are unavailable due to temporary technical issues. Please try again later.
  • Dimensions Drawings

    Dimensions



  • Mounting and Clearance

    Mounting on a Rail



    Direct Mounting on a Panel Surface


    (1)
    Install a mounting strip

    Mounting Hole Layout



    Mounting
    Correct Mounting Position


    Acceptable Mounting Position


    Incorrect Mounting Position



    Clearance



  • Connections and Schema

    Digital Inputs
    Wiring Diagram (Positive Logic)


    (*)
    Type T fuse

    Wiring Diagram (Negative Logic)


    (*)
    Type T fuse

    Connection of the Fast Inputs



    Relay Outputs
    Positive Logic (Sink)


    (*)
    Type T fuse
    (1)
    The COM0, COM1 and COM2 terminals are not connected internally.
    (2)
    To improve the life time of the contacts, and to protect from potential inductive load damage, you must connect a free wheeling diode in parallel to each inductive DC load or an RC snubber in parallel of each inductive AC load

    Negative Logic (Source)


    (*)
    Type T fuse
    (1)
    The COM0, COM1 and COM2 terminals are not connected internally.
    (2)
    To improve the life time of the contacts, and to protect from potential inductive load damage, you must connect a free wheeling diode in parallel to each inductive DC load or an RC snubber in parallel of each inductive AC load


    Analog Inputs



    The (-) poles are connected internally.

    Pin

    Wire Color

    0 V

    Black

    AN1

    Red

    0 V

    Black

    AN0

    Red


    Ethernet Connection


    Pin N°

    Signal

    1

    TD+

    2

    TD-

    3

    RD+

    4

    -

    5

    -

    6

    RD-

    7

    -

    8

    -



    USB Mini-B Connection



    SL1 Connection


    SL1

    N °

    RS 232

    RS 485

    1

    RxD

    N.C.

    2

    TxD

    N.C.

    3

    RTS

    N.C.

    4

    N.C.

    D1 (A+)

    5

    N.C.

    D0 (B–)

    6

    CTS

    N.C.

    7

    N.C.

    5 Vdc

    8

    Common

    Common

    N.C.: not connected



  • Performance Curves

    Derating Curves
    Embedded Digital Inputs (No Cartridge)


    X :
    Ambient temperature
    Y :
    Input simultaneous ON ratio

    Embedded Digital Inputs (with Cartridge)


    X :
    Ambient temperature
    Y :